Changing or Replacing UNIGATE® CO(M)-ProfibusDP by UNIGATE® CX-C4Map-PBDPV1

Aus Deutschmann Wiki
Zur Navigation springen Zur Suche springen

The table below describes which points need to be observed when changing or replacing UNIGATE® CO(M)-ProfibusDP by UNIGATE® CX-C4Map-PBDPV1. In addition to the information on the hardware and software, this also contains information on the EPLAN files so that the documentation can be adapted accordingly if necessary.

UNIGATE® CO(M)-ProfibusDP UNIGATE® CX Note
UNIGATE CO(M) - ProfibusDP.png
UNIGATE CX-CO-PB.jpg
UNIGATE® CX: UNIGATE® CX is only available in housing colour Grey.
Protocol Green check.svg Green check.svg (*see note) UNIGATE® CX-C4Map: UNIGATE® CX-C4Map-PBDPV1 contains the CANopen Mapping. Via the configuration software WINGATE, the CANopen Mapping can be done. UNIGATE® CX-C4Map-PBDPV1 can thus be used like the UNIGATE® CO(M)-ProfibusDP.
Software
Konfigurationssoftware WINGATE Green check.svg Green check.svg UNIGATE® CX: The configuration file (*.gwc) of UNIGATE® CO(M) - ProfibusDP can not be loaded inUNIGATE® CX-C4Map-PBDPV1.
Mechanics
Housing WxHxD 90 x 127 x 55 mm 46 x 117 x 106 mm
Protection type IP24 IP20
Connection-Power Supply Mounting Position
Frontal-Bottom Bottom
screw-plug-connector 2 pol.
screw-plug-connectorr X1 and X2
Power Supply screw-plug-connector 2 pol. screw-plug-connector 4 pol. X1 screw-plug-connector 4 pol. X2
+24V/DC (Pwr) Pin 1 Pin 1 Red x.svg UNIGATE® CX: The power supply is internally bridged between + 24V/DC (Pwr) and + 24V/DC (Out) as well as between 0V (GND) (Pwr) and 0V (GND) (Out). This only has to be done at + 24V/DC (Pwr) and 0V (GND) (Pwr).
0V (GND) (Pwr) Pin 2 Pin 2 Red x.svg
+24V/DC (Out) Red x.svg Red x.svg Pin 1
0V (GND) (Out) Red x.svg Red x.svg Pin 2
Housing-Earthing Earthing Clamp via DIN-Rail Earthing Clamp via DIN-Rail
UNIGATE CO(M) - ProfibusDP (Housing-Earthing)
UNIGATE CX (Housing-Earthing)
UNIGATE® CO(M) - ProfibusDP: At elder devices the earthing is done by flat plug connectors or there is no earthing at the device.
Example shows UNIGATE CO(M) - ProfibusDP
Anschluss-Seriell Mounting Position
Side Part - right Top Bottom
For 3 pol. screw-plug-connector
screw-plug-connector Service Interfaces
screw-plug-connector X1 und X2
Application Interface (RS232) screw-plug-connector 3 pol. screw-plug-connector 3 pol. Service Interfaces Red x.svg
Rx Pin 1 Pin 1 Red x.svg
Tx Pin 2 Pin 2 Red x.svg
AP-GND Pin 3 Pin 3 Red x.svg
Debug-Interface Red x.svg Red x.svg screw-plug-connector 4 pol. X1

screw-plug-connector 4 pol. X2

Rx-Debug Red x.svg Red x.svg Pin 3
Tx-Debug Red x.svg Red x.svg Pin 4
Selection Application Interface Not selectable Configurable
RS232 Green check.svg Green check.svg (*see note) Red x.svg UNIGATE® CX: The RS232 interface is used exclusively as a service interface. For example, a 'Reset device' or a 'Firmware Update' (* .hex) can be carried out via this.
Application- Interface Rotary Coding Switches & LEDs Mounting Position
Frontal Frontal
application interface LEDs
application interface rotary coding switches & LEDs
Rotary Coding Switch S4 Red x.svg Green check.svg UNIGATE® CX: Operating modes may be selected correspondingly as at UNIGATE® CO(M) - ProfibusDP. Attention: Switch position "DD" is reserved for internal use and is not allowed to use.
Rotary Coding Switch S5 Red x.svg Green check.svg
LED Power Red x.svg Green check.svg
LED State Red x.svg Green check.svg
LEDs 1/2/4/8 (Error No / Select ID) Green check.svg Green check.svg
Connection Fieldbus Mounting Position
Frontal-Top Frontal-Bottom Frontal Top
CANopen Red x.svg
connection via 9 pol. D-Sub connector
connection via 9 pol. D-Sub connector
Red x.svg
PROFIBUS
connection via 9 pol. D-Sub socket
Red x.svg
connection via 9 pol. D-Sub socket
Red x.svg
Termination Connectible by slide switch Connectible by slide switch
Fieldbus Rotary Coding Switches & LEDs Mounting Position
Frontal-Top Frontal Bottom Frontal
CANopen Red x.svg
fieldbus Dip-Switch & LEDs
CANopen Dip-Switch & LEDs
Dip-Switch Red x.svg Green check.svg Green check.svg
LED BUS Power Red x.svg Green check.svg Green check.svg
LED BUS State Red x.svg Green check.svg Green check.svg
PROFIBUS
fieldbus rotary-coding-switches & LEDs
Red x.svg
PROFIBUS rotary-coding-switches & LEDs
Rotary Coding Switch High Green check.svg Red x.svg Green check.svg
Rotary Coding Switch LOW Green check.svg Red x.svg Green check.svg
LED BUS Power Green check.svg Red x.svg Green check.svg
LED BUS Error Green check.svg Red x.svg Green check.svg
LED BUS State Green check.svg Red x.svg Green check.svg
Device Description Files
CANopen Red x.svg Green check.svg UNIGATE® CX: An EDS - file can be generated by configuration software WINGATE.
PROFIBUS DPV0 DAGW2862.gsd UGIC3218.gsd UNIGATE® CX: The GSD file for the PROFIBUS can be downloaded from the homepage. GSD-Datei (GSD-File) Icon (DIB-File)
PROFIBUS DPV1 Red x.svg UGIC3218.gsd UNIGATE® CX: The GSD file for the PROFIBUS can be downloaded from the homepage. GSD-Datei (GSD-File) Icon (DIB-File)
EPLAN
CANopen Red x.svg Green check.svg UNIGATE® CX: The macro for EPLAN can be downloaded from the homepage. EPLAN - Makro Unigate CL-C4 (Zip-Datei) Compatibility list macros UNIGATE® CL/CX (PDF-File)
PROFIBUS Red x.svg Green check.svg UNIGATE® CX: The macro for EPLAN can be downloaded from the homepage. EPLAN - Makro Unigate CL-PB (Zip-Datei) Compatibility list macros UNIGATE® CL/CX (PDF-File)

Green check.svg = available
Red x.svg = not available
Further detailed information may be found in the corresponding manual in chapter "Technical Data".