LOCON 200 (English): Unterschied zwischen den Versionen
Reith (Diskussion | Beiträge) |
Reith (Diskussion | Beiträge) |
||
Zeile 57: | Zeile 57: | ||
'''Note:''' The setting via the rotary coding switches is done in ''hexadecimal''.<br /> | '''Note:''' The setting via the rotary coding switches is done in ''hexadecimal''.<br /> | ||
In LOCON 200-PB two modes are selectable through WINLOC32 via the PROFIBUS-Interface. | In LOCON 200-PB two modes are selectable through WINLOC32 via the PROFIBUS-Interface. | ||
− | * '''S7-Modus''' (ex-works condition): For an operation at a Simatic S7 and for use of the [[Data | + | * '''S7-Modus''' (ex-works condition): For an operation at a Simatic S7 and for use of the [[Data Component Simulator]]. |
* '''Communication Profile Mode''': For the Operation via the [[#Weblinks|Communication Profile for Deutschmann cam controls]]. | * '''Communication Profile Mode''': For the Operation via the [[#Weblinks|Communication Profile for Deutschmann cam controls]]. | ||
The PROFIBUS-Address (Slave-ID) is set by factory setting on 126 (decimal). | The PROFIBUS-Address (Slave-ID) is set by factory setting on 126 (decimal). |
Version vom 15. Mai 2014, 16:39 Uhr
Inhaltsverzeichnis
Konfiguration
By factory setting all LOCON 200 cam controls are configured as follows:
- Outputs: 16
- Encoder Type: SSI Singleturn
- Real Encoder resolution: 4096
- Virtual Encoder resolution: 4096
- Idle time: Bitwise
This configuration set by default may be changed by using TERM 6 or the software WINLOC 32.
Programming
LOCON 200 can be programmed by TERM 6 or TERM 24 or the software WINLOC 32. The PROFIBUS-Version can be programmed also by PROFIBUS.
Device versions
LOCON 200
LOCON 200 features a serial RS232-interface and a RS485-(DICNET) interface, the needed setting is made through the corresponding rotary coding switches High und Low , located at the bottom side of the device.
High | Low | Meaning |
---|---|---|
D | DICNET-Adress | DICNET-Operation, Bus Termination inactive |
E | DICNET-Adress | DICNET-Operation, Bus Termination active |
F | F | RS232-Operation |
Only the DICNET-Addresses 0 ... 15 (decimal) are supported (right rotary coding switch Low = DICNET-Address). Examples:
High | Low | Meaning |
---|---|---|
D | 3 | bus termination inactive, DICNET-Address 3 |
E | C | bus termination active, DICNET-Address 12 |
'Note: The setting via the rotary coding switches is done in hexadecimal.
LOCON 200-PB (PROFIBUS)
LOCON 200-PB (PROFIBUS) is always PROFIBUS-Slave and features a serial RS232-interface and a PROFIBUS-Interface, instead of the RS485-(DICNET) Interface, the needed setting is made through the corresponding rotary coding switches High und Low , located at the bottom side of the device.
High | Low | Meaning |
---|---|---|
0 | 0 | PROFIBUS-operation, external address assignment |
0 | 1 | PROFIBUS-operation, Adress 1 |
… | ||
7 | D | PROFIBUS-operation, Adress 125 |
7 | E | PROFIBUS-operation, external address assignment |
F | F | RS232-operation |
Note: The setting via the rotary coding switches is done in hexadecimal.
In LOCON 200-PB two modes are selectable through WINLOC32 via the PROFIBUS-Interface.
- S7-Modus (ex-works condition): For an operation at a Simatic S7 and for use of the Data Component Simulator.
- Communication Profile Mode: For the Operation via the Communication Profile for Deutschmann cam controls.
The PROFIBUS-Address (Slave-ID) is set by factory setting on 126 (decimal). If the rotary coding switch is on position "00" und "7E" then any desired address can be assigned either through WINLOC32 or the PROFIBUS-Master. The GSD-file (L200.GSD) and a S7-example project are available for download on our homepage. Further information regarding LOCON 200-PB can be found in the manual Cam Controls with Fieldbus-Connection. LOCON 200-Out I/O8 (extension module)== LOCON 200-Out I/O8 is an extension module and contains 8 I/Os. With this extension module the basic device LOCON 200 resp. (-PB)) can be expanded by 8 I/Os step-by-step to a maximum configuration level of 144 I/Os (incl. the 16 I/Os of LOCON 200 resp. (-PB). LOCON 200-Out I/O8 contains an own processor. Therefore, the switching accuracy (cycle time) is independent of the LOCON 200(-PB) Basic module).
Weblinks
- Handbuch für das LOCON 200 (PDF-Datei)
- GSD-Datei für das LOCON 200-PB
- S7-Beispiel-Projekt (ZIP-Datei)
- Handbuch Kommunikationsprofil für Deutschmann Nockensteuerungen (PDF-Datei)
- Handbuch Nockensteuerungen mit Feldbusanbindung (PDF-Datei)