UNIGATE® interfaces: Unterschied zwischen den Versionen
Zur Navigation springen
Zur Suche springen
Reith (Diskussion | Beiträge) (Die Seite wurde neu angelegt: „== PC COM-Port == Nachfolgend wird die Belegung eines PC-COM-Port beschrieben. {| class="wikitable" |+Anschluss |- ! colspan="1" align="center" | UNIGATE® …“) |
Reith (Diskussion | Beiträge) |
||
(19 dazwischenliegende Versionen desselben Benutzers werden nicht angezeigt) | |||
Zeile 1: | Zeile 1: | ||
== PC COM-Port == | == PC COM-Port == | ||
− | + | Hereafter follows a description of the PC-COM-Port assignment. | |
{| class="wikitable" | {| class="wikitable" | ||
− | |+ | + | |+Connection |
|- | |- | ||
! colspan="1" align="center" | UNIGATE® !! colspan="2" align="center" | PC COM-Port (9 pol. D-Sub) | ! colspan="1" align="center" | UNIGATE® !! colspan="2" align="center" | PC COM-Port (9 pol. D-Sub) | ||
|- | |- | ||
− | ! | + | ! Assignment !! Pin !! Assignment |
|- | |- | ||
| Rx / Rx-Debug / DbgRx || 3 || Tx | | Rx / Rx-Debug / DbgRx || 3 || Tx | ||
Zeile 15: | Zeile 15: | ||
|- | |- | ||
| Appl.-GND / GND / 0V || 5 || GND | | Appl.-GND / GND / 0V || 5 || GND | ||
+ | |- | ||
+ | |} | ||
+ | |||
+ | == Application Interface(RS232)== | ||
+ | Please find hereafter an assignment description for each UNIGATE, which are needed for connection to a PC COM-Port. | ||
+ | |||
+ | {| class="wikitable" | ||
+ | |+Connection | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® CL | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | X1 || 1 || Rx | ||
+ | |- | ||
+ | | X1 || 2 || Tx | ||
+ | |- | ||
+ | | X1 || 3 || Appl.-GND | ||
+ | |- | ||
+ | | colspan="3" align="left" | '''Attention:''' For devices with '''Option I/O8''' information regarding debug via Application Interface is available in the respective manual. | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® CL (Option GT) | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | X1 || 1 || Rx | ||
+ | |- | ||
+ | | X1 || 2 || Tx | ||
+ | |- | ||
+ | | X1 || 3 || Appl.-GND | ||
+ | |- | ||
+ | | colspan="3" align="left" | '''Attention:''' For devices with '''Option I/O8''' information regarding debug via Application Interface is available in the respective manual. | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® CM | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | X1 || 1 || Rx | ||
+ | |- | ||
+ | | X1 || 2 || Tx | ||
+ | |- | ||
+ | | X1 || 3 || Appl.-GND | ||
+ | |- | ||
+ | | colspan="3" align="left" | '''Attention:''' Information regarding debug via Application Interface is to be found in the manual. | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® EL | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | X1 || 1 || Rx | ||
+ | |- | ||
+ | | X1 || 2 || Tx | ||
+ | |- | ||
+ | | X1 || 3 || Appl.-GND | ||
+ | |- | ||
+ | | colspan="3" align="left" | '''Attention:''' Information regarding debug via Application Interface is to be found in the manual. | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® FC | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | - || 17 || Rx | ||
+ | |- | ||
+ | | - || 18 || Tx | ||
+ | |- | ||
+ | | - || 12 || GND | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® MB | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | X1 || 1 || Rx | ||
+ | |- | ||
+ | | X1 || 2 || Tx | ||
+ | |- | ||
+ | | X1 || 3 || Appl.-GND | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® IC | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | - || 29 || Rx | ||
+ | |- | ||
+ | | - || 30 || Tx | ||
+ | |- | ||
+ | | - || 24 || GND | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® RS | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignement | ||
+ | |- | ||
+ | | Screw-Plug-Connector 5pol. || 3 || Rx | ||
+ | |- | ||
+ | | Screw-Plug-Connector 5pol. || 4 || Tx | ||
+ | |- | ||
+ | | Screw-Plug-Connector 5pol. || 5 || GND | ||
+ | |- | ||
+ | | colspan="3" align="left" | '''Note:''' Application Interface has to be set by slide switch to '''RS232'''. | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® SC | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | Screw-Plug-Connector 5pol. || 3 || Rx | ||
+ | |- | ||
+ | | Screw-Plug-Connector 5pol. || 4 || Tx | ||
+ | |- | ||
+ | | Screw-Plug-Connector 5pol. || 5 || GND | ||
+ | |- | ||
+ | | colspan="3" align="left" | '''Note:''' Application Interface has to be set by slide switch to '''RS232'''. | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® SC (Option Debug) | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | (9 pol. D-Sub) || 2 || Rx | ||
+ | |- | ||
+ | | (9 pol. D-Sub) || 3 || Tx | ||
+ | |- | ||
+ | | (9 pol. D-Sub) || 5 || GND | ||
+ | |- | ||
+ | | colspan="3" align="left" | '''Note:''' Application Interface has to be set by slide switch to '''RS232'''. | ||
+ | |- | ||
+ | |} | ||
+ | |||
+ | == Debug-Interface == | ||
+ | Please find hereafter an assignment description for each UNIGATE, which are needed for connection to a PC COM-Port. | ||
+ | {| class="wikitable" | ||
+ | |+Connection | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® CL | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | X2 || 3 || Rx-Debug | ||
+ | |- | ||
+ | | X2 || 4 || Tx-Debug | ||
+ | |- | ||
+ | | X1 || 3 || Appl.-GND | ||
+ | |- | ||
+ | | colspan="3" align="left" | '''Attention:''' Not in connection with Option I/O8 | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® CL (Option GT) | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | X2 || 3 || Rx-Debug | ||
+ | |- | ||
+ | | X2 || 4 || Tx-Debug | ||
+ | |- | ||
+ | | X1 || 3 || Appl.-GND | ||
+ | |- | ||
+ | | colspan="3" align="left" | '''Attention:''' Not in connection with Option I/O8 | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® CX (1. device) | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | X1 || 3 || Rx-Debug | ||
+ | |- | ||
+ | | X1 || 4 || Tx-Debug | ||
+ | |- | ||
+ | | X1 || 2 || 0V | ||
+ | |- | ||
+ | | colspan="3" align="left" | '''Note:''' At the communication of the first device the power supply may be connected at plug X2 Pins 1 and 2 of the second device. | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® CX (2. device) | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | X2 || 3 || Rx-Debug | ||
+ | |- | ||
+ | | X2 || 4 || Tx-Debug | ||
+ | |- | ||
+ | | X2 || 2 || 0V | ||
+ | |- | ||
+ | | colspan="3" align="left" | '''Note:''' At the communication of the second device the power supply may be connected at plug X1 Pins 1 and 2 of the first device. | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® FC | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | - || 16 || DbgRx | ||
+ | |- | ||
+ | | - || 15 || DbgTx | ||
+ | |- | ||
+ | | - || 12 || GND | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® IC | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | - || 28 || DbgRx | ||
+ | |- | ||
+ | | - || 27 || DbgTx | ||
+ | |- | ||
+ | | - || 24 || GND | ||
+ | |- | ||
+ | ! colspan="3" align="center" | UNIGATE® SC (Option Debug) | ||
+ | |- | ||
+ | ! Plug !! Pin !! Assignment | ||
+ | |- | ||
+ | | (9 pol. D-Sub) || 9 || RxD | ||
+ | |- | ||
+ | | (9 pol. D-Sub) || 4 || TxD | ||
+ | |- | ||
+ | | (9 pol. D-Sub) || 5 || GND | ||
+ | |- | ||
+ | | colspan="3" align="left" | '''Note:''' Application Interface has to be set by slide switch to '''RS232'''. | ||
|- | |- | ||
|} | |} |
Aktuelle Version vom 11. Mai 2016, 11:03 Uhr
PC COM-Port
Hereafter follows a description of the PC-COM-Port assignment.
UNIGATE® | PC COM-Port (9 pol. D-Sub) | |
---|---|---|
Assignment | Pin | Assignment |
Rx / Rx-Debug / DbgRx | 3 | Tx |
Tx / Tx-Debug / DbgTx | 2 | Rx |
Appl.-GND / GND / 0V | 5 | GND |
Application Interface(RS232)
Please find hereafter an assignment description for each UNIGATE, which are needed for connection to a PC COM-Port.
UNIGATE® CL | ||
---|---|---|
Plug | Pin | Assignment |
X1 | 1 | Rx |
X1 | 2 | Tx |
X1 | 3 | Appl.-GND |
Attention: For devices with Option I/O8 information regarding debug via Application Interface is available in the respective manual. | ||
UNIGATE® CL (Option GT) | ||
Plug | Pin | Assignment |
X1 | 1 | Rx |
X1 | 2 | Tx |
X1 | 3 | Appl.-GND |
Attention: For devices with Option I/O8 information regarding debug via Application Interface is available in the respective manual. | ||
UNIGATE® CM | ||
Plug | Pin | Assignment |
X1 | 1 | Rx |
X1 | 2 | Tx |
X1 | 3 | Appl.-GND |
Attention: Information regarding debug via Application Interface is to be found in the manual. | ||
UNIGATE® EL | ||
Plug | Pin | Assignment |
X1 | 1 | Rx |
X1 | 2 | Tx |
X1 | 3 | Appl.-GND |
Attention: Information regarding debug via Application Interface is to be found in the manual. | ||
UNIGATE® FC | ||
Plug | Pin | Assignment |
- | 17 | Rx |
- | 18 | Tx |
- | 12 | GND |
UNIGATE® MB | ||
Plug | Pin | Assignment |
X1 | 1 | Rx |
X1 | 2 | Tx |
X1 | 3 | Appl.-GND |
UNIGATE® IC | ||
Plug | Pin | Assignment |
- | 29 | Rx |
- | 30 | Tx |
- | 24 | GND |
UNIGATE® RS | ||
Plug | Pin | Assignement |
Screw-Plug-Connector 5pol. | 3 | Rx |
Screw-Plug-Connector 5pol. | 4 | Tx |
Screw-Plug-Connector 5pol. | 5 | GND |
Note: Application Interface has to be set by slide switch to RS232. | ||
UNIGATE® SC | ||
Plug | Pin | Assignment |
Screw-Plug-Connector 5pol. | 3 | Rx |
Screw-Plug-Connector 5pol. | 4 | Tx |
Screw-Plug-Connector 5pol. | 5 | GND |
Note: Application Interface has to be set by slide switch to RS232. | ||
UNIGATE® SC (Option Debug) | ||
Plug | Pin | Assignment |
(9 pol. D-Sub) | 2 | Rx |
(9 pol. D-Sub) | 3 | Tx |
(9 pol. D-Sub) | 5 | GND |
Note: Application Interface has to be set by slide switch to RS232. |
Debug-Interface
Please find hereafter an assignment description for each UNIGATE, which are needed for connection to a PC COM-Port.
UNIGATE® CL | ||
---|---|---|
Plug | Pin | Assignment |
X2 | 3 | Rx-Debug |
X2 | 4 | Tx-Debug |
X1 | 3 | Appl.-GND |
Attention: Not in connection with Option I/O8 | ||
UNIGATE® CL (Option GT) | ||
Plug | Pin | Assignment |
X2 | 3 | Rx-Debug |
X2 | 4 | Tx-Debug |
X1 | 3 | Appl.-GND |
Attention: Not in connection with Option I/O8 | ||
UNIGATE® CX (1. device) | ||
Plug | Pin | Assignment |
X1 | 3 | Rx-Debug |
X1 | 4 | Tx-Debug |
X1 | 2 | 0V |
Note: At the communication of the first device the power supply may be connected at plug X2 Pins 1 and 2 of the second device. | ||
UNIGATE® CX (2. device) | ||
Plug | Pin | Assignment |
X2 | 3 | Rx-Debug |
X2 | 4 | Tx-Debug |
X2 | 2 | 0V |
Note: At the communication of the second device the power supply may be connected at plug X1 Pins 1 and 2 of the first device. | ||
UNIGATE® FC | ||
Plug | Pin | Assignment |
- | 16 | DbgRx |
- | 15 | DbgTx |
- | 12 | GND |
UNIGATE® IC | ||
Plug | Pin | Assignment |
- | 28 | DbgRx |
- | 27 | DbgTx |
- | 24 | GND |
UNIGATE® SC (Option Debug) | ||
Plug | Pin | Assignment |
(9 pol. D-Sub) | 9 | RxD |
(9 pol. D-Sub) | 4 | TxD |
(9 pol. D-Sub) | 5 | GND |
Note: Application Interface has to be set by slide switch to RS232. |