UNIGATE CO (M)-PROFIBUS DP - I encountered problems after downloading the existing/old GWC-file into my new device. Can you list the various steps?
- Open the desired GWC file with the configuration tool WINGATE.
- Then start the new device and perform the download
- Now perform an Upload from the device
- The parameter "CAN baud rate" is now at 125k.
- If the baudrate is set using the DIP switch you have to change the parameter. Therefor the parameter has to be selected. By double-clicking a window opens in which the "DIP switch" has to be selected.
- Afterwards perform another download
- Save the change, respectively the "new" GWC file
In a further download of these "new" GWC files into a new device the "CAN baud rate" parameter is now set accordingly and doesn't have to be changed again.
How to replace CANopen (Master) - PROFIBUS DP (Slave)?
- Start WINGATE:
- Connect the RS232 from PC to UNIGATE (3 wire, 3 pin connector)
- Connect power supply
- Upload file
- Save file
- Disconnect the old UNIGATE
- Connect the new UNIGATE (see Step 1)
- Afterwards click "File - Download" (write to device)
In WINGATE-File the Adresse 0x14 is set to 0
With the new Firmware V2.60 in WINGATE the config file has to be stored with the setting "baud rate: DIP Switch"